Blog
Medical waste incineration system

Medical waste incineration system of 300 kg/hr burn rate with dual fuel (gas and diesel) type, daily 8-16 hrs operation and a stack height of 15 meter.Primary combustion
i.    The primary combustion chamber shall be accepted as the primary combustion zone;
ii.    The minimum combustion temperature of the primary chamber shall not be less than 800 degrees C;

Secondary combustion
The residence time in the secondary chamber shall not be less than 2 seconds;
The gas temperature as measured against the inside wall in the secondary chamber, not in the flame zone, shall not be less than as indicated in Lots 1-7 ;
Both the primary and the secondary temperatures shall be maintained until all the waste has been completely combusted;

Chimney
The chimney shall have a minimum height of 4 meters above ground level;
The minimum exit velocity of the emissions shall not be less than 10 metres/second;1.    Capacity of destruction in weight: 60 Kg/h.
2.    It should be able to operate not less than 10 hours/day
3.    This incinerator must be able to destruct all combustible wastes produced by hospitals, private clinics, laboratories, institutes, etc…
4.    Design Specification : Types A, B, C, D, and E of medical waste
5.    “PYROLYTIC” combustion, by controlling the gasification of waste.
6.    The incinerator must avoid the release of black smoke and fine dust, (Smokeless) during the loadings.
7.    It should be able to reduce the volume of wastes by 98%.
8.    It should be able to hold emission in the second burn with gas residence of not less than 2 seconds.
9.    The incineration should be completely free from visible smoke as well as offensive odours.
10.    The lower calorific power (L.C.P) of this waste will be 3,500 kcal/kg
•    The Temperatures of combustion: Minimum will be 850oC and max 1400oC
•    Post combustion: >1100oC.
11.    The Internal diameter of the Chimney: Ø 400 and its height: 8 m
12.    The Volume of the combustion chamber: 1.200 L
13.    The Dimension of the door for loading in cm: 70×70.
14.    Burner operation should be Automatic On/Off
15.    Fuel : diesel
16.    The supplier must provide  necessary information for the best of  the installation
This incinerator with “PYROLYTIC” combustion must have:
17.    A combustion chamber of waste:
* Perfectly tight door for the manual loading of waste. The loading should be Manual, Batch Load
* A burner of lighting which the use is limited to the ignition of waste.
* Frontage of loading with door seals gone up on hinges, wheel of screw plug, flexible joint, and stuffing insulating out of refractory.
* The insulation of the combustion chamber should be composed of refractory bricks, having a high content of aluminium and insulates bricks in order to assure a minimum temperature on   the outside sheet metal.
* Composition of the refractory;
•    Refractory concrete :
    . Thickness    : ≥100 mm
    . Nature: 42% of Al203
•    Insulate in fibrous panels :
    . Thickness: ≥75 mm
•    Nature: Calcium silicate.
* Burner of lighting of waste, with fuel, standard mono-bloc casting guiding  plunging flame, lighting and safety of electronic ignition, permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.
* Plate of combustion in Carborundum, avoiding the fixing of glass and slags.

18.    A chamber of post combustion of gases
* A burner of combustion of gases,
* A device of injection of air allowing a total recombustion of gases,
* A device of air inlet of cooling of waste gases,
* A sheath of evacuation of the gases burnt.
* Carcass in strong sheet steel with support of connection.
* Composition of the refractory;
•    Refractory concrete :
    Thickness    : ≥150 mm
    Nature: 65% of Al203
•    Insulate in fibrous panel :
    Thickness: ≥85 mm
     Nature: Calcium
* Burner with fuel, mono-bloc casting guiding type with horizontal flame, lighting and safety of     electronic ignition, permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.
* A secondary injection of air to ensure perfect oxygen content.
19.    A control box ensuring the complete cycle of combustion.

20.    Fan:
* Electro-ventilator distributing the secondary air, the regulation of the air flow being carried out by valves and following the control of the automatic cycle.
21.    Controls and regulations:
Control box watertight to dust, including:

* A switch circuit breaker for each engine (ventilators and burners).
* A timer with adjustable temporization for the regulation of each burner.
* A regulator with digital watching for the temperature of combustion.
* A regulator with digital watching for the temperature of postcombustion.
* Electric box.

21. The de- ashing must be done in the bottom of the combustion chamber or the deashing should be Automatic or manual batch de ashing.
22. Process Filtering system: Scruber to be mentionned as optional
23. Emission Standards Compliance: BS 3316 or équivalent standard
23. Capacity to treat Plastic: Not less than 40% by weight
24. CE Manufacturing Compliance: BS EN 746-2-1997
22.    The supplier must give batches of spare parts of first urgency and consumable of the incinerator.
23.    The installed incinerator must bear a one year guarantee.
24.    The supplier shall perforn an onsite installation of the incinerator.
25.    The technical training of operators will have to be provided and given by a technician
from the factory; it will consist of curative and preventive maintenance, and the use of machine, etc

Blog
Hiclover waste incinerator

Key Features:

— Full range incinerator with Economized Small Scale incinerator, Standard Small-Large Scale incinerator, 

General Municipal Solid Waste Incinerator, Pet and Animal Cremation, Containerized Mobile Incinerator, 

High Efficient Environmental Waste Incinerator.

— Single combustion chamber, double combustion chambers, three combustion chambers and 

multi-combustion chambers waste incinerators.

— System solutions for medical waste environmental.

— High burn rate, from 5kgs to 1000kgs per hour.

— New Design for pet animal cremation business.

— HICLOVER, trusted partner with years of experience.

HICLOVER, Nanjing Clover Medical Technology Co.,Ltd, supply system solutions for medical environmental 

protection, animal and pet cremation engineering, other municipal solid waste incineration project.

We supply single combustion chamber, double combustion chambers, three combustion chambers and 

multi-combustion chambers waste incinerators for laboratory, clinic, hospital, medical center, hygiene 

clinical waste destruction with medical disposable, biological waste, medical plastic waste, hazardous waste, 

red bag waste, needle disposal, gauze and bandages, sealed sharp containers, pathological waste, trace-chemotherapeutic wastes, etc.

      

Our range of incinerators cater for small to large scale animal cremation related businesses, such as poultry farms, 

cattle farms, sheep farms, pig farms, stables, kennels, testing laboratory, catteries, pet crematoriums.

The incinerator burn waste in primary combustion chamber and burn the smoke from primary combustion chamber 

again to make sure environmentally friendly with no black smoke, smelless, reduce pathogenic bacteria infection.

System solutions for medical waste environmental, including waste incineration, smoke emission treatment, 

high-temperature sterilization, ultraviolet sterilization lamp, waste shredder, needle destroyer, medical waste 

package, sharp containers, etc.

The pet cremation equipment humanized design with movable platform, small space covers for modern pet 

cremation business owner all over the world.

The containerized mobile incinerator mounted in ISO container before leave factory, pre-installation, no 

incineration house build construction, movable by truck and ultraviolet lamp sterilization inside.

HICLOVER is growing brand for environmental protection field, and market share with most of Africa, 

Middle East, Southeast Asia countries and part of North America, Europe territory. We are trusted partner 

for governmental organizations, non-profit organizations, international contractors, logistics organizations, 

military, pet cremation business owners, etc. We have export experience more than 40 countries, including 

war zone like Iraq, Afghanistan, Somalia, South Sudan.

We are china incinerator manufacturer, contractor and exporter. Manufacturer make reasonable price for 

incinerator customer, supply medical incinerator, hospital incinerator, animal incinerators, hog incinerators, 

pet cremation equipment, small incinerator, pet incinerator, animal incinerator, portable incinerator, small 

animal incinerator, infectious waste pyrolysis machine, laboratory incinerator. HICLOVER help customer 

reduce purchase budget, custom made function, quality products and friendly service.



HICLOVER – Medical Environmental 


 

Waste Incinerators
Medical Waste Incinerator
Pet Animal Cremation
Solid Waste Incinerator

Tel:  +86-25-8461 0201   
Mobile: +86-13813931455(whatsapp/wechat)
Website: www.hiclover.com  
Email: [email protected]
Email: [email protected]  
Nanjing Clover Medical Technology Co.,Ltd.

 

2020-02-12

Blog
Various Types of Incinerators

hazardous waste high temperature incinerators for the treatment of hazardous wastes. The waste will be mixed, including medical, oily wastes, woods and laboratory wastes. Primary combustion
Diesel/LPG/LNG burning primary combustion chamber/primary combustion zone
Secondary combustion
Residence time in the secondary chamber not less than 2 seconds
Both primary and the secondary temperatures maintained until all the waste has been completely combusted
Chimney
Chimney with a minimum height of 4 meters above ground level
Minimum exit velocity of the emissions not less than 10 metres/second
Temperature Warnings
Audible and/or visible alarm to warn the operator when the secondary temperature drops to below the required temperature
General
Control box that can be detached and mounted on separate stand at least 1.5 meters from incinerator at approximately 1.6 meter height

Incinerator model A
Burn Rate 65kg/h minimum
Weight (kg), please indicate:
Secondary Chamber
Gas Retention Time – 2 Seconds
Fuel – Diesel/LPG/LNG, please indicate
Power Supply for Control Box – 220V-240V 50Hz single phase
Minimum operating temperature 850 °C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
I000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height
Warranty, indicate no of years

Incinerator model B
Burn Rate 150kg/h minimum
Weight (kg), please indicate:
Secondary Chamber
Gas Retention Time – 2 Seconds
Diesel/LPG/LNG, please indicate
Power Supply for Control Box- 220V-240V 50Hz single phase
Minimum operating temperature 920 °C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
I000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height
Warranty, indicate no of years

Incinerator model C
Burn Rate 250kg/h minimum
Weight (kg) please indicate:
Secondary Chamber
Gas Retention Time 2 Seconds
Fuel Diesel/LPG/LNG, please indicate
Power Supply for Control Box 220V-240V 50Hz single phase
Minimum operating temperature 920 °C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
I000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height
Warranty, indicate no of years

Lot 4 – High Temperature Waste Incinerator
HTW Incinerator model D
Burn Rate – 150kg/hour minimum
Weight (kg), please indicate:
Secondary Chamber
Gas Retention Time 2 Seconds
Fuel Diesel/LPG/LNG, please indicate
Power Supply for Control Box 220V-240V, single phase 50-60Hz
Minimum operating temperature 1200°C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
1000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height
Warranty, indicate no of years

Lot 5 – Mobile Incinerator
Mobile Incinerator model E
Burn Rate 50kg/h minimum
Weight (kg), please indicate:
Secondary Chamber
Gas Retention Time – 2 Seconds
Fuel – Diesel/LPG/LNG, please indicate
Power Supply for Control Box – 220V-240V 50Hz single phase
Minimum operating temperature 850 °C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
1000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height
Warranty, indicate no of years

Lot 6 – Mobile Incinerator
Mobile Incinerator model F
Burn Rate 100kg/h minimum
Weight (kg), please indicate:
Secondary Chamber
Gas Retention Time – 2 Seconds
Fuel – Diesel/LPG/LNG, please indicate
Power Supply for Control Box – 220V-240V 50Hz single phase
Minimum operating temperature 850 °C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
1000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height
Warranty, indicate no of years

Lot 7 – High Temperature Waste Mobile Incinerator
HTW Mobile Incinerator model G
Burn Rate 100kg/h minimum
Weight (kg), please indicate:
Secondary Chamber
Gas Retention Time – 2 Seconds
Fuel – Diesel/LPG/LNG, please indicate
Power Supply for Control Box – 220V-240V 50Hz single phase
Minimum operating temperature 1200 °C, please indicate
One year Spare Parts Package for complete maintainability
10m Hose Pipe, indicate length
1000 Litre Fuel Tank + Pipe System, indicate volume
Additional chimney extension, indicate height

Blog
Waste Incinerators for Livestock and Hatchery Operations in the Republic of Congo

Supplying Waste Incinerators for Livestock and Hatchery Operations in the Republic of Congo

As part of ongoing efforts to modernize agricultural and veterinary waste management, the Ministry of Agriculture, Livestock and Fisheries of the Republic of Congo has expressed interest in acquiring a biological waste incinerator suitable for handling complex waste streams generated from livestock and hatchery operations.
This includes non-hatched chicks, infertile eggs, placentas, animal carcasses, and pathological waste—all classified as high-risk biological waste requiring safe, controlled destruction.


Proposal from HICLOVER

Requirement Proposed by HICLOVER
Model TS100 or equivalent – Yes, we recommend Model TS100
Capacity ~100 kg per cycle – Yes, designed for 100–150 kg per feeding, particularly for animal waste
Preferred fuel Mixed (Diesel + Electric power supply) – Yes, our incinerators support diesel burners with electric controls
Destination Port of Pointe-Noire, Republic of Congo – Yes, shipping and logistics can be arranged directly

The TS100 is a robust, dual-chamber incinerator engineered for biological waste, featuring:

  • High combustion temperature (>850°C in secondary chamber) to ensure pathogen destruction.

  • Diesel-fueled primary combustion supported by an electric PLC control system.

  • Average throughput designed for ~100 kg per batch, scalable based on feeding frequency.

  • Heavy-duty refractory lining to withstand daily agricultural and hatchery operations.


Waste Incineration Needs in the Republic of Congo

The Republic of Congo, like many Central African countries, faces increasing demand for environmentally compliant biological waste disposal, especially in:

  • Large-scale poultry hatcheries dealing with non-hatched chicks and infertile eggs.

  • Veterinary laboratories and livestock operations generating pathological waste, animal carcasses, and placental remains.

  • Slaughterhouses and meat processing units.

Historically, many farms and facilities relied on open burning or simple single-chamber brick incinerators. These older methods:

  • Fail to reach the high temperatures required for complete pathogen destruction.

  • Produce visible smoke, odor, and significant particulate emissions.

  • Do not comply with modern environmental and veterinary health standards.


Import and Market Trends

The Republic of Congo largely imports incinerators due to limited local manufacturing capacity for specialized equipment. Over the past five years, government ministries, NGOs, and private agribusinesses have procured:

  • Small and medium-sized dual-chamber diesel-fired incinerators.

  • Mobile or containerized units for field use in remote agricultural zones.

  • Incinerators with electronic controls and better emissions management.

Growing urbanization, stricter veterinary regulations, and international support (from FAO, OIE, and development banks) have accelerated this trend.


Why Choose HICLOVER TS100 for Agricultural Biological Waste?

Technical advantages:

  • Specifically engineered for dense organic waste like poultry and livestock remains.

  • Dual combustion chambers to reduce smoke and odor.

  • Flexible installation: can be fixed, skid-mounted, or containerized.

  • Electric-powered control panel with temperature monitoring and auto-start.

Operational benefits:

  • Average capacity per batch suits medium-scale hatcheries and livestock operations.

  • Fast burning cycle keeps pace with daily waste generation.

  • Heavy refractory lining ensures durability, even with high-moisture animal waste.

Environmental compliance:

  • Meets WHO and FAO recommendations for biological waste disposal.

  • High-temperature combustion significantly reduces pathogen load and odor.

  • Ash volume reduced to less than 5–10% of original waste volume.


Shipping and Support

HICLOVER can arrange direct delivery to Port of Pointe-Noire, Republic of Congo, the country’s principal seaport.
We also offer:

  • On-site installation guidance.

  • Operator training.

  • Spare parts and after-sales technical support.


By selecting the TS100 biological waste incinerator, the Ministry of Agriculture, Livestock and Fisheries of the Republic of Congo—and other agricultural stakeholders—can:

  • Improve farm and hatchery biosecurity.

  • Meet modern veterinary health standards.

  • Reduce environmental impact compared to open burning.

For detailed technical specifications, price quotations, or references from similar African projects, please visit:
www.hiclover.com
sales@hiclover.com

HICLOVER – providing reliable, high-temperature waste treatment solutions for agriculture, veterinary, and medical sectors across Africa.


Mobile: +86-13813931455(WhatsApp)

Email:     sales@hiclover.com     
Blog
Incinerator for Animal Crematory Pig Farm Model A1200

Incinerator for Animal Crematory Pig Farm Model A1200


*** 3 sets Burners
*** Good for animals or big pets
*** Double Combustion chamber
*** stainless steel chimney
*** Italy made oil burners
*** 1200Liters(1.2m3) big chamber

Model

A1200

Picture

Burning Rate

Average 50 kgs/hour

Feed Capacity

Average 100 kgs/feeding

Primary Combustion Chamber

1200 Liters

Secondary Combustion Chamber

500 Liters

Mix Combustion Chamber

Yes

Smoke Filter Chamber

Yes(Dry Scrubber)

Feed Mode

Manual

Voltage

220V/380V

Fuel Type

Diesel Oil

Burner

Italy Original

Oil Consumption (Diesel Oil)

Average 34.4 kg/hour

Gas Consumption (Natural Gas)

***

Internal Dimensions

130x100x90cm (primary chamber)

External Dimensions

220x180x360cm (without chimney)

Temperature Monitor

Yes

Oil Tank Capacity(if oil fuel)

500 Liters

Door Opening

55 x 80cm

Chimney Length

10.0 Meters

Chimney Type

Stainless Steel

Equipment Gross Weight

7500 kgs

Operation Technical Specifications

Primary Chamber Temperature

800-1000

Secondary Chamber Temperature

1000-1200

Residency Time

2.0 Sec.

Burning Efficiency

98%

Waste Lower Calorific Power

3000Kcal

Model

A1200

Internal Dimensions

130x100x90 cm

Suit for Animal

Cat – yes

Dog – yes

Pig – small

Cow – no

Main Product List

Primary Combustion Chamber

Secondary Combustion Chamber

Mix-Combustion Chamber

Smoke Filter Chamber(Dry Scrubber)

Incinerator Control Case

Chimney:10.0Meters *(upgrade to Stainless Steel, free cost)

Italy oil burner: 03 sets

Oil Tank : 500Liters

HICLOVER – Medical Environmental 


 

Waste Incinerators
Medical Waste Incinerator
Pet Animal Cremation
Solid Waste Incinerator

Tel:  +86-25-8461 0201   
Mobile: +86-13813931455(whatsapp/wechat)
Website: www.hiclover.com  
Email: [email protected]
Email: [email protected]  
Nanjing Clover Medical Technology Co.,Ltd.

 

2020-02-11

Blog
Medical Waste Management and Incinerator Use in Burundi

Medical Waste Management and Incinerator Use in Burundi

Burundi, a small East African country with a population of around 13 million, faces challenges in safely managing healthcare waste. Its healthcare system includes:

  • A network of national hospitals, district hospitals, and local health centers

  • Growing numbers of NGO-supported clinics, especially in rural and border areas

Most health facilities generate infectious waste: used syringes, dressings, laboratory waste, and small amounts of pathological and pharmaceutical waste.


Waste Treatment Practices

Historically, many facilities relied on:

  • Simple single-chamber brick incinerators, often locally built

  • Open pit burning or burial behind facilities, which pose public health and environmental risks

  • Occasional transport of limited quantities of hazardous waste to centralized sites in larger towns

Such methods often fail to reach the high temperatures (≥850°C) needed to safely destroy pathogens and reduce harmful emissions.


Introduction of Modern Incinerators

In the past decade, improvements have come through:

  • International donor-funded projects (e.g., WHO, UNICEF, Gavi, and the Global Fund) supporting installation of safer, dual-chamber incinerators

  • Procurement of small to medium-capacity diesel-fired incinerators, often 10C50 kg/hour, suitable for hospitals and district health centers

  • Some incinerators installed as part of maternal and child health and vaccination programs to handle increased volumes of sharps and used PPE


Examples of Facilities Using Incinerators

While detailed national lists are limited, known sites include:

  • Centre Hospitalo-Universitaire de Kamenge (CHUK) in Bujumbura, the capital: reported to operate a higher-capacity dual-chamber incinerator serving the hospital and surrounding facilities

  • Ngozi Regional Hospital and Gitega Regional Hospital: have small diesel-fired incinerators, partly funded by donor programs

  • Selected district hospitals and communal health centers equipped with smaller, locally built brick incinerators or imported compact incinerators

NGO-supported field hospitals and refugee health posts, particularly near the Tanzania border, have also deployed containerized mobile incinerators to manage periodic spikes in medical waste.


Technical and Environmental Trends

  • Shift from single-chamber to dual-chamber units: better pathogen destruction and fewer visible emissions

  • Growing demand for compact, containerized incinerators: suitable for remote rural areas where waste transport is not practical

  • Consideration of wet scrubber systems or chimney extensions to reduce particulate emissions, especially in urban hospitals

  • Emphasis on operator training and maintenance support, often bundled with equipment purchases to ensure long-term usability


Remaining Challenges

  • Limited budget allocation by public health authorities means continued dependence on donor-funded procurement

  • Many rural health centers still rely on low-efficiency incinerators or uncontrolled burning

  • A need to update national guidelines and enforce standards on temperature monitoring and emission controls

Burundi is gradually improving medical waste treatment by installing modern, dual-chamber incinerators, especially in key hospitals and through donor-supported programs. Compact, mobile, and containerized models―such as those offered by HICLOVER―are particularly suited for Burundi’s mix of small rural facilities and larger district hospitals, offering safe and practical solutions where infrastructure is limited.

For technical details, tailored proposals, or examples of compact incinerators ideal for Burundi’s health sector, visit:
www.hiclover.com
or contact: sales@hiclover.com


Mobile: +86-13813931455(WhatsApp)

Email:     sales@hiclover.com     
Blog
Medical Incinerators Manufacturer in China
*** Primary combustion chamber & secondary combustion chamber
*** Smoke filter chamber(dry scrubber)
*** stainless steel chimney
*** PLC auto. control
*** Italy made oil or gas burner(diesel oil/natural gas/lpg)
*** temperature display and control
*** high temperature firebrick,etc
Items/Model TS10(PLC) TS20(PLC) TS30(PLC) TS50(PLC) TS100(PLC)
Burn Rate (Average) 10 kg/hour 20 kg/hour 30 kg/hour 50 kg/hour 100 kg/hour
Feed Capacity(Average) 20kg 40kg 60kg 100kg 200 kg
Control Mode PLC PLC PLC PLC PLC
Combustion Chamber 100L 210L 330L 560L 1200L
Internal Dimensions 50x50x40cm 65x65x50cm 75x75x60cm 100x80x70cm 120x100x100cm
Secondary Chamber 50L 110L 180L 280L 600L
Smoke Filter Chamber Yes Yes Yes Yes Yes
Feed Mode Manual Manual Manual Manual Manual
Voltage 220V 220V 220V 220V 220V
Power 0.5Kw 0.5Kw 0.5Kw 0.7Kw 0.7Kw
Oil Consumption (kg/hour) 5.4–12.6 7.8–16.3 10.2–20 12.1–24 14–28
Gas Consumption (m3/hour) 6.2–11.4 8–15.7 9.8–20 9.9–26.1 10–32.2
Temperature Monitor Yes Yes Yes Yes Yes
Temperature Protection Yes Yes Yes Yes Yes
Oil Tank 100L 100L 100L 100L 200L
Feed Door 30x30cm 45x40cm 55x50cm 70x55cm 80x60cm
Chimney 3Meter 3Meter 5Meter 5Meter 10Meter
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel
1st. Chamber Temperature 800–1000 800–1000 800–1000 800–1000 800–1000
2nd. Chamber Temperature 1000-1200 1000-1200 1000-1200 1000-1200 1000-1200
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Gross Weight 1500kg 2200kg 3000kg 4500kg 6000kg
External Dimensions 140x90x120cm 160x110x130cm 175x120x140cm 230x130x155cm 260x150x180cm
HICLOVER – Medical Environmental 


 

Waste Incinerators
Medical Waste Incinerator
Pet Animal Cremation
Solid Waste Incinerator

Tel:  +86-25-8461 0201   
Mobile: +86-13813931455(whatsapp/wechat)
Website: www.hiclover.com  
Email: [email protected]
Email: [email protected]  
Nanjing Clover Medical Technology Co.,Ltd.

 

2020-02-10

Blog
durable and highly efficient incinerators with various capacities for hospital/medical waste, cremation and other solid waste treatments

Single and Dual Chamber Medical Incinerator.durable and highly efficient incinerators with various capacities for hospital/medical waste, cremation and other solid waste treatments.

 

Chamber Double

Burning Rate      10 kg per hour (for two incinerators)

Burning Rate     20 kg per hour (for three incinerators)

Loading   Method   Manual

No of Burners   Single for 10 kg/hour and Double for 20 kg per hour

Fuel                    Diesel and Natural Gas

Warm Up Time    Not more than 20 minutes

Temperature controller   Digital

Power Supply      Single Phase 220V

Chimney Height    20 feet from ground level

·         50kg per hour

·         Option for  medical waste.

Type
Single Chambered Cylindrical

Feed Material
Papers, Cartons wastes

Capacity
1000 Kg/Day

Burning Capacity
125 Kg/hr

Design Standards
Generally confirming to IS Standards

Type of burning operation
Zero Fuel System

Combustion Chamber

Type
Cylindrical

Dimension
1.25 m Dia (Approx) x 1.2 m Height (Approx)

Temperature
400 – 600 °C

MOC
Chrome Alloy Steel, inside lining with fire bricks/Ceramic Clay

Outer Lining
Thermal Proof Lining

STACK

Type
Self Supported

MOC
MS

Accessories
Port Hole and Ladder for emission testing with complete online scrubbing system, thermostat

The units will be used for our client camps in the field. These Camps range in manning size from 20 – 200 people. Each site has a medical clinic, a very small use for medical but will need it.

Blog
Double Combustion Chamber Incinerators 30kgs per hour
*** Double Combustion Chamber
*** PLC auto control operation
*** stainless steel chimney
*** smoke filter chamber
*** Italy oil/gas burner
*** whole design, mini. installation working
*** cheaper cost
*** long lifetime design
*** better material and spare parts

Items/Model

TS30(PLC)

Picture

 

Burn Rate

Average 30 kg/hour

Feed Capacity

Average 60kg per feeding

Control Mode

PLC(Programmable Logic Controller Incinerator)

Combustion Chamber

330L

Internal Dimensions

75x75x60cm

Secondary Chamber

180L

Smoke Filter Chamber

Yes

Feed Mode

Manual Feeding

Voltage

220V

Power

0.5Kw

Oil Consumption (kg/hour)

Average 13.3

Gas Consumption (N.G, m3n/Hour)

Average 16

Gas Consumption (L.P.G, m3n/Hour)

Average 11.7

Temperature Monitor

Four Digital Display

Temperature Protection

Yes

Oil Tank

100L or More(Optional)

Feed Door

55x50cm

Chimney

5Meter or More(Optional)

Chimney Type

Stainless Steel

1st. Chamber Temperature

800-1000

2nd. Chamber Temperature

1000-1200

Residency Time

2.0 Sec.

Gross Weight

4000kg

External Dimensions

175x120x140cm


Item

Specification

Model

TS30 PLC

Main Product List per 01 set

Primary Combustion Chamber

Secondary Combustion Chamber

Smoke Filter Chamber

Incinerator PLC Control Case

Chimney:5.0Meters

*(upgrade to Stainless Steel, free cost)

Italy oil/gas burner: 02 sets

Oil Tank (if oil fuel): 100Liters


HICLOVER – Medical Environmental 


 

Waste Incinerators
Medical Waste Incinerator
Pet Animal Cremation
Solid Waste Incinerator

Tel:  +86-25-8461 0201   
Mobile: +86-13813931455(whatsapp/wechat)
Website: www.hiclover.com  
Email: [email protected]
Email: [email protected]  
Nanjing Clover Medical Technology Co.,Ltd.

 

2020-02-10

Blog
Medical Waste Incinerator of 20 kg/hr capacity with dual burner

3 Medical Waste Incinerator of 20 kg/hr capacity with dual burner.Medical Waste Incineration Systems. i’m interested to destroy about 200 kg remains. a Medical Incinerator project for Tehran municipality. Our purpose for this project is to establish a plant in order to incinerate Medical waste with 50 ton/day capacity. a incinerator with 100 kg / hour burning capacity. And it should work on diesel fuel, 2 chamber. Waste management
Incinerator
*External diameter at base 6ft 1.8m
*External diameter at top 4 1/2ft 1.35m
*Internal diameter at base 3ft 0.9m
*Internal diameter at top 3ft 0.9m
*Thickness of wall at base 18cm
*Thickness of wall at top 9cm
*Perpendicular height of wall 4ft
*Height of Iron bars from grate above ground 1ft

Material Required
*Puddle swish
*5 or 6 Iron bars about 4 1/2ft 1.35m long each
*Quantity of large stones for foundation
*2 empty kerosene tins for making vent holes
*2ltrs of coal tar
*2 brushes
*Foundation 1ft-1 1/2ft deep is dug
*Filled with large stones and puddle swish to ground level
*Empty kero tins are next placed into position where the vent holes are to appear
*Wall 1ft high is built with puddle swish
*Iron bars are put in position leaving a space of about 2cm-3cm between the bars 4ft 1.2m to be reached
*Wall plastered smooth.Incinération à haute température pour la destruction complète des déchets contaminés ou dangereux.
Principe de combustion pyrolytique avec brûlage des fumées dans une chambre de post-combustion
Incinérateur double chambre 900°C/1200°C de capacité 30 kg.
Equipé de : 1 brûleur de combustion + 1 brûleur de re-combustion + 1 laveur de fumées. Capacité de destruction horaire
En poids : au moins 30 kg
En volume : au moins 200 litres
Température :
Combustion : 900°C
Post combustion : 1200°C
Puissance des brûleurs
Combustion : au moins 80 KW
Post combustion : 80 KW
Puissance électrique : environ 2 KW
Cheminée :
Section : environ 30×30 cm
Hauteur (minimum) : au moins 8 m
Dimension de la porte de chargement : environ 50X50 cm

HICLOVER